MV75 |
MV85 |
MV95 |
MV95FR |
CarboPleat |
DuoPleat |
| Rated Air Flow (cfm) |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
| Average Dust Spot Efficiency (%)* |
80 |
85 |
96 |
96 |
N/A |
95 |
| Initial Efficiency on Particles >1 micron (%) |
>69 |
>71 |
>93.5 |
>93.5 |
N/A |
>91 |
| Initial Resistance(in. w.g.) |
0.24 |
0.27 |
0.30 |
0.30 |
0.30 |
0.44 |
| Max.Temperature(ºF) |
160, peaks 175 |
160, peaks 175 |
160, peaks 175 |
160, peaks 175 |
160 |
160 |
| UL 900 Classification |
Class 2 |
Class 2 |
Class 2 |
Class 1 |
- |
- |
| Depth(in) |
11.5 |
11.5 |
11.5 |
11.5 |
11.5 |
11.5 |
| Size Availability |
1/1, 5/6, 5/5,1/2 |
1/1, 5/6, 5/5,1/2 |
1/1, 5/6, 5/5,1/2 |
1/1, 5/6, 5/5,1/2 |
1/1, 5/6, 5/5,1/2 |
1/1, 5/6, 5/5,1/2 |
* According to ASHRAE 52.1 - 1992
For more information, call us at 1-888-924-6233.
|